In RapidCore the transducer is known as
“Auxiliary Sensor 5” and is located under Sensors > Auxiliary Senser 5.
Name
Range
Description
Signal Source
Sub Menu
----
Signal Source >
Source
Disable
Port A
Port B
Port C
Port D
The sensor input to use for the Transducer feature or set to
Disable to disable this feature.
Signal Source >
Display
Enable
Disable
Set to enable to display the value of the transducer and the
tank icon when the controller is in Run Mode.
Signal Source >
Start On
Disable, Low, High
Set an automatic start when signal goes below or above
the Start threshold.
Signal Source >
Offset
-50.0 ~ 50.0
in 0.1 increments
This applies an offset to the transducer value. This can be
used for calibration.
Sender Type
Custom
TF1 115F/R240
TF2 231F/R240
TP1 200P/R240
TP2 100P/R240
The sender table to use. A custom sender table can be
defined (using the RapidCore Configurator Software) or
one of four predefined sender tables can be selected.
TF1/TF2 are float sensors; 115F/R240 means it has a
range of 115 °F at 240
Ω.
TP1/TP2 are pressure sensors; contact Cattron at
for more information.
Start Stop
Sub Menu
----
Start Stop >
Bypass Time
0 ~ 90 s
in 1 s increments
For warnings/failures, this sets the amount of time to ignore
the input when Run Mode is first entered.
For automatic start (if enabled), this sets the amount of
time to ignore the input when Auto Mode is first entered.
No warnings, failures or start will be triggered during this
time even if normally they would be triggered.
Start Stop > Run
Time
1 ~ 6000 min
in 1 min increments
Disabled
The length of time to run the engine on a Low or High
AutoStart.
Start Stop > Start
0.1 ~ 510 in 0.1 °F / % /
ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The threshold at which to start the engine. The
“Start On”
setting above determines which direction the threshold
must be crossed.
Start Stop > Stop
0.1 ~ 510 in 0.1 °F / %
/ ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The threshold at which to stop the engine. The
“Start On”
setting above determines which direction the threshold
must be crossed.
Thresholds
Sub Menu
-----
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...