DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
49
9M02-9249-A001-EN
Revision A
Name
Range
Description
RPM Settings >
Rated RPM
500 ~ 4000 RPM
in 1 RPM increments
This is a mirror of the same setting under Sensors >
Engine Speed. It determines the final engine speed.
RPM Settings >
Goal RPM
500 ~ 4000 RPM
in 1 RPM increments
This is a mirror of the
“Goal Speed” setting under Other
Config > Pump System.
Dwell Times
Sub Menu
-----
Dwell Times >
Warm-up
0 ~ 600 s
in 5 s increments
This is a mirror of the
“Warmup Time” setting under Timers
> Engine Logic.
Dwell Times >
Interm
1 to 300 s
in 1 s increments
This is a mirror of the
“Interm Delay” setting under Other
Config > Pump System.
Dwell Times >
Cooldown
0 ~ 600 s
in 5 s increments
This is a mirror of the
“Cooldown Time” setting under
Timers > Engine Logic.
Ramp Times
Sub Menu
-----
Ramp Times >
Dwell 1 (Idle to
Intermediate)
1 ~ 300 s
in 1 s increments
These are mirrors of the same settings under Other Config
>
Ramp Times >
Dwell 2
(Intermediate to
Rated)
1 ~ 300 s
in 1 s increments
Ramp Times >
Dwell 3 (Rated to
Idle)
1 ~ 300 s
in 1 s increments
Ramp Times >
TSC1 RPM/s
Disable
10 ~ 300 RPM/s
in 10 RPM/s increments
This is a mirror of the same setting under Sensors >
Engine Speed. Changes in engine speed are limited to this
maximum.
Bump Speed
Disable
0 ~ 500 RPM
in 1 RPM increments
This is a mirror of the same setting under Other Config >
Pump System. It determines the increment in engine speed
when doing a manual speed adjustment.
5.2.1.3
Transducer Menu
This menu controls the settings for the Transducer input. This is an input similar to the Auxiliary Sensors under
Sensors. Warnings and failures can be set as well as start on low or start on high start conditions.
The transducer input differs from the auxiliary sensors in three ways:
•
The warnings/failures and start conditions can both be active at the same time instead of choosing one
or the other as in the auxiliary sensors
•
There is an option to show a tank display or ambient temperature. See the
for more information
•
For pressure, the custom sender table can have negative values (down to -10 PSI)
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...