Event Name
Event Type
Description
Reset Defaults
Event
The controller has loaded default settings. This could have been
because the user initiated a factory reset from the RapidCore software
or because the controller memory has become corrupt. The controller
will need to be programmed with the proper settings if applicable.
Service Complete
Event
The tech has performed service on the engine/generator and has reset
the maintenance counter as mentioned in
“Service Required” above.
Exerciser Bypass
Event
The exerciser, if enabled under Timers > Exerciser, has been skipped.
This could happen if the controller was otherwise running or powered
off when an exerciser was scheduled to be performed.
Start Exercise
Event
The controller has auto started to perform an exercise.
Stop Exercise
Event
The controller has run for the programmed exercise and is now
shutting down.
Log Cleared
Event
The controller Events History has been cleared either from user action
(via the RapidCore software) or because the controller memory was
corrupt.
Modbus Start
Event
The controller has auto started from a start command sent to its
RS485 Modbus port.
Modbus Stop
Event
The controller has auto stopped from a stop command sent to its
RS485 Modbus port.
Genset Disable
Event
Applies to the Kubota electronic engine. Level 3 shutdown has
occurred.
Engine Started
Event
The engine has successfully started and entered the Run Mode.
J1939 Remote
Event
The controller has auto started due to a command sent over its CAN
J1939 port.
Idle Speed
Event
The controller has entered Idle Mode either from the idle switched
input, the warmup or cooldown idle feature under Engine Logic, or for
some other reason. Under speed, under frequency, and under voltage
warnings and failures are disabled.
Rated Speed
Event
The controller has exited Idle Mode and has gone back into normal
running.
Sensor 1 Run
Event
The controller has auto started due to an Auxiliary Sensor 1
“start on
low
” or “start on high” request.
Sensor 2 Run
Event
The controller has auto started due to an Auxiliary Sensor 2
“start on
low
” or “start on high” request.
Sensor 1 Stop
Event
The controller has shut down due to an Auxiliary Sensor 1
“start on
low
” or “start on high” stop request.
Sensor 2 Stop
Event
The controller has shut down due to an Auxiliary Sensor 2
“start on
low
” or “start on high” stop request.
Switch Start
Event
A controller start was triggered by the momentary start switched input.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...