DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
89
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
RPM Disconnect
100 ~ 2000 RPM
650 RPM
Speed at which controller determines the
engine has started successfully and turns
off the Crank output.
Postheat Time
0 ~ 90 s
0 s
Amount of time the Glowplug output
remains on after crank success and the
engine is running.
False Restart
(Restart on False
Start)
Enable false start (engine stall) detection. Refer to the
False Check (False
Restart Detect
Time)
Warmup Time
0 ~ 600 s
in 5 s increments
0 s
After successful cranking, engine delays
this amount of time before turning on the
Warmup output. This allows the engine to
warm up before applying any load to it.
The output will turn off when the controller
enters the Cooldown Delay.
Cooldown
Shutdown
Force Cooldown
Shutdown
The function the OFF button on the front
panel performs while engine is running.
See the
OFF Button Function
section for
more information.
Cooldown Time
0 ~ 6000 s
in 5 s increments
0 s
Amount of time to cool down the engine
after a stop command has been received.
During this time the Warmup output turns
off and the Cooldown output turns on. If
another start command is received during
cool down, the controller will return to
Running Mode.
ETS On Duration
(Energize to Stop)
0 ~ 30 s
0 s
Amount of time the Energize to Stop (ETS)
output is on after the engine has shut
down. Time must be greater than 0 s for
the Energize to Stop function to work.
As of TG350/TG410 version 1.88, the OFF
button is disabled during ETS to prevent
possible issues with the engine failing to
shut down.
If controller still detects speed (RPM)
above 600 RPM in the last two seconds, it
goes to a
‘
Failures
’ failure.
Warm-up Idle
Idle options. See the
section for more information.
Idle Settings
Cooldown Idle
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...