Switched Inputs
The controller has five switched inputs which cause the controller to perform a function when activated. The
following are the default settings.
Default Settings
Switched Input
Default Value
Switched Input A
Emergency Stop
Switched Input B
Start / Stop
Switched Input C
Disable
Switched Input D
Disable
Switched Input E
Disable
Switched I/O > Switched IN X:
Name
Range
Description
Function
[Menu] See below.
The function that the switched input performs when active.
Active Mode
[Menu] See below.
Determines the operating conditions under which the switched
input can be active. Multiple selections are allowed.
Trigger
[Menu] See below.
The state of the input determining if it is active or inactive.
Switched I/O > Switched IN X > Function:
Name
Active Mode
Description
Disabled
N/A
Input is disabled and has no function.
Start / Stop
Auto, Running
Starts the engine when active, stops the engine when
deactivated. It is recommended that the Trigger mode be set to
Close +BAT for better noise tolerance.
If Trigger mode is set to
“Open” or “Close +BAT/GND”, the
start/stop input will act like a momentary input. A pulse of
2 to 4 seconds will start controller. Another pulse of 2 to 4
seconds is required to stop the controller. If the input is just
turned off, the controller will continue to run.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...