Revision A
Name
Parent Menu
Range
Default
Description
Warmup
Idle
Timers >
Engine Logic
Disable
Warm-up Timer
Oil Temp.
Engine Temp.
Disable
If enabled, the engine is placed in Idle
Mode during the warm-up period.
Warm-up Timer
– The engine idles during
the duration of the warm-up timer
countdown.
Oil Temp.
– The oil temperature over
J1939 is used to determine the extent of
the Warm-up / Idle period.
Engine Temp.
– Same as Oil Temp. but
the engine temperature is used. The
engine temperature can come locally or
from J1939.
The oil temp and engine temp selections
use the Debounce, Low Point, and High
Point settings below.
Debounce
Timers >
Engine Logic >
Idle Settings
1 to 10 s,
in 1 s increments
10 s
(Warmup Idle) If the temperature remains
between the
“Low Point” and “High Point”
settings for this time, exit the warm-up /
idle.
Low Point
Timers >
Engine Logic >
Idle Settings
1 to 180 °F,
in 1 °F increments
32 °F
(Warmup Idle) Continue to idle when the
temperature is below this setting. Ignore
the Debounce.
High Point
Timers >
Engine Logic >
Idle Settings
1 to 180 °F,
in 1 °F increments
50 °F
(Warmup Idle) Always exit idle when the
temperature is above this setting.
5.6.1.4.2
Remote Start Inhibit in Idle
Use this feature to prevent start up when the Idle Mode switch is active.
Settings (Other Config > Idle Inhibit, in the Configurator Software; these are under the switched inputs
when the idle input is enabled)
Name
Parent Menu
Range
Default
Description
Remote Start
(Start / Stop
Switched Input
Inhibit)
Other Config >
Idle Inhibit
No Inhibit
Inhibit
No Inhibit
Prevent the remote start switch input from
starting the engine when the idle switch is
active.
Aux Start (Aux 1,
2, 3, 4 Sensor
AutoStart Inhibit)
Other Config >
Idle Inhibit
No Inhibit
Inhibit
No Inhibit
Prevent Auxiliary 1, 2, 3, and 4 sensors
AutoStart feature from starting the engine
when the idle switch is active.
If the engine is in the Idle Mode because of the
feature, the remote start (start/stop) and auxiliary
sensors AutoStart can still start the engine.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...