DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
92
9M02-9249-A001-EN
Revision A
This section explains the general Idle functionality. There are three ways to use Idle, as follows:
•
Warmup Idle
– Automatically enter the Idle Mode during warmup for a period of time before going to
rated speed; see
•
Cooldown Idle
– Idle automatically during cool down; see below
•
Idle Switched Input
– Idle whenever this switched input is active; see the Idle Mode function under
Name
Parent Menu
Range
Default
Description
Warmup
Idle
Timers >
Engine Logic
Disable
Warm-up Timer
Oil Temp.
Engine Temp.
Refer to the
Idle
Settings
Timers >
Engine Logic
[Menu]
Cooldown
Idle
Timers >
Engine Logic
Disable
Enable
Disable
Idle during cooldown.
Auto Idle
Link
Timers >
Engine Logic
Disable
Breaker Trip
Disable
If set to breaker trip, the breaker trip will
be activated whenever the controller is in
the Idle Mode. The breaker trip will be
turned off when Idle Mode is exited if it
was not in the latched state.
If the user de-laches the breaker trip
output while Auto Idle is active, the
breaker trip will turn off for 1 second and
then turn back on.
Idle Switched Output
A switched output can be set to Idle to turn on whenever Idle Mode is entered. This is useful for electronic
governors that have an idle input to tell the governor to run the engine at idle speed. Note that the switched
outputs are meant to drive relays, so a relay must be installed to do the logic for the governor.
5.6.1.4.1
Warmup Idle
This section explains the Warmup Idle functionality.
The Warmup Idle is used to run the engine at a reduced speed at engine start.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...