Thresholds > Low
Warn
Disable
0.1 ~ 510 in 0.1 °F / %
/ ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The low warning setpoint. Active in Run and Cooldown
Modes.
Thresholds > Low
Fail
Disable
0.1 ~ 510 in 0.1 °F / %
/ ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The low failure setpoint. Active in Run and Cooldown
Modes.
Thresholds > High
Warn
Disable
0.1 ~ 510 in 0.1 °F / %
/ ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The high warning setpoint. Active in Run and Cooldown
Modes.
Thresholds > High
Fail
Disable
0.1 ~ 510 in 0.1 °F / %
/ ft increments
-9.9 ~ 500 in 0.1 PSI
increments
The high failure setpoint. Active in Run and Cooldown
Modes.
When the transducer is enabled when the controller is in the Run Mode, a tank graphic will be displayed.
5.2.1.4
Closed Loop Menu
These settings mirror those of the same name in Other Config > Process Control.
Name
Range
Description
Parameters
Sub Menu
-----
Parameters > Delay
1 ~ 30 s
in 0.1 s increments
The control loop delay and gain. The Delay and Gain
settings affect how regressive the control is to changes.
Parameters > Gain
1 ~ 30
in 0.1 increments
Maintain
Sub Menu
-----
Maintain > Main-In
1 ~ 900
in 0.1 increments
The goal value to maintain when the process control
feature is set to Maintain-In or Maintain-Out. Engine speed
is adjusted to maintain these values. Only one it used at
any given time. See Maintain Setup setting in Application >
Function menu.
Maintain > Main-Out
1 ~ 900
in 0.1 increments
Maintain >
D
1 ~ 30
in 0.1 increments
Values in this range do not cause any change in engine
speed.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...