Event Name
Event Type
Description
Over Voltage
Warning
The generator AC voltage has risen above the over voltage warning
setpoint set under AC Monitor > Genset Voltage. Possible issue with
the voltage regulator or speed governor on the engine.
High Fuel Temp
Warning
Doosan G2 electronic engine high fuel temperature warning. This
warning comes from the engine ECM over CAN J1939.
Hi Exhaust Temp
Warning
Doosan G2 electronic engine high turbine exhaust temperature. This
warning comes from the engine ECM over CAN J1939.
Transducer Low
Warning
The transducer (aka Auxiliary Sensor 5) reading has fallen below the
transducer low warning setpoint set under Application Menu >
Transducer menu.
Transducer High
Warning
The transducer (aka Auxiliary Sensor 5) reading has risen above the
transducer high warning setpoint set under Application Menu >
Transducer menu.
Failed To Stop
Failure
The controller shut down the engine -- by turning off the Fuel output
and (if enabled) by turning on the Energize-To-Stop output -- but the
engine speed did not go to zero after the energize to stop time (under
Timers > Engine Logic).
Breaker Failed
Failure
The
“Breaker Trip” switched output failed to turn off the breaker. This
is triggered if the AC Current is still above 10% of the rated current
setpoint. The
“breaker trip” failure has to be enabled under AC Monitor
> O.C. Protection > Brk Trip Fail.
Load Imbalance
Failure
The generator load is imbalanced between the A, B, and C phases.
This has to be enabled under AC Monitor > O.C. Protection >
Imbalance Mode with the mode set to
“Shutdown Trip.”
Over Current
Failure
The generator AC current has risen above the over current failure
setpoint set under AC Monitor > O.C. Protection > Basic Alarm.
ECM Shutdown
Failure
Electronic engines only. CAN J1939 DM1 stop lamp is active; the ECM
has shut down the engine.
High Engine Temp
Failure
Engine temperature has risen above the high engine temperature
failure setpoint set under Sensors > Engine Temp.
Low Oil Pressure
Failure
Engine oil pressure has fallen below the low oil pressure failure
setpoint set under Sensors > Oil Pressure.
Under Speed
Failure
Engine speed has fallen below the under speed failure setpoint set
under Sensors > Engine Speed.
Over Speed
Failure
Engine speed has risen above the over speed failure setpoint set
under Sensors > Engine Speed.
Low Fuel Level
Failure
The fuel level has fallen below the low fuel level failure setpoint under
Sensors > Fuel Level.
Low Battery
Failure
The main starter battery (the battery from which the controller is
powered) voltage has fallen below the low battery failure setpoint set
under Sensors > Battery.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...