DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
105
9M02-9249-A001-EN
Revision A
5.7.3.4
Dummy Load
The dummy load feature can be enabled to prevent wet stacking.
AC Monitor > Genset Current > Dummy Load
Name
Range
Default
Description
Bypass Time
Disabled
1 ~ 120 s
in 1 s intervals
Disabled
The amount of time to delay before applying
the dummy load.
Load On
Disabled
1 ~ 500 A
in 1 A increments
Disabled
The threshold below which the dummy load
is applied. There is a 4 second debounce
time. The bypass time must expire before the
load is applied. All phases must drop below
this threshold to trigger the dummy load.
Load Off
Disabled
1 ~ 500 A
in 1 A increments
Disabled
The threshold above which the dummy load
is removed. The dummy load is turned off if
one phase rises above this threshold.
One of the
must also be set to dummy load. The output is only turned on when the engine is
running.
5.7.3.5
EPS Supplying Load
The EPS (Emergency Power System) Supplying Load sets a flag in Modbus register 40006 to indicate to the
Cattron RA400 remote annunciator that the generator is actively supplying power. If this flag is set, the
RA400 will light its EPS Supplying Load indicator. This is used to meet NFPA110 requirements.
If the actual current measured on any one phase of the generator is above 5% of the AC over current warning
set point, then the EPS Supplying Load flag is set. For more information on this register, refer to the TOUGH
Series Modbus Reference Manual or the RA400 manual.
5.8
Communications
The controller has the ability to communicate with other systems over communication buses. The following
sections relate to settings associated with communications.
5.8.1 CANbus (J1939)
This page gives a very short overview of J1939 support (electronic engines). For detailed information about
J1939 and all related settings, please refer to the J1939 Reference Manual, which can be found at
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...