DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
110
9M02-9249-A001-EN
Revision A
In RapidCore:
•
The ramp settings are located under Sensors > Engine Speed > Speed Settings
•
The float control and tank maximum settings are located under Pumping Applications
Name
Range
Description
RUN Button (Manual
RUN Button)
Run Only
Run&Throttle
Controls when the user can manually adjust the
engine speed when the controller is started by a
manual run.
“Run Only” means the speed can only be
adjusted once the engine speed has reached the
goal speed.
“Run&Throttle” means the speed can be
adjusted once the engine has reached idle.
Ramp Setting
Sub menu
-----
Ramp Setting >
Goal Speed
500 ~ 4000 RPM
in 1 RPM increments
The final speed after the speed ramping is finished.
Ramp Setting >
Bump Speed
Disable
0 ~ 500 RPM
in 1 RPM increments
The maximum amount the user is allowed to adjust
the speed.
Ramp Setting >
Interm Speed
(Intermediate Speed)
500 ~ 4000 RPM
in 1 RPM increments
The speed between the idle and goal speeds.
Ramp Setting >
Interm Delay
(Intermediate Delay)
1 ~ 300 s
in 1 s increments
The amount of time to remain at the intermediate
speed.
Ramp Time
Sub menu
-----
Ramp Time > Dwell 1
(Idle to Intermediate)*
1 ~ 300 s
in 1 s increments
The amount of time to ramp from the idle to
intermediate speed.
Ramp Time > Dwell 2
(Intermediate to
Rated)*
1 ~ 300 s
in 1 s increments
The amount of time to ramp from the intermediate to
goal speed.
Ramp Time > Dwell 3
(Rated to Idle)*
1 ~ 300 s
in 1 s increments
The amount of time - in addition to the cooldown time
- to ramp from the goal speed to the idle speed.
Float Control
Disable
Fill Tank
Empty Tank
Float control can AutoStart the engine if one of the
switched input functions is set to the float function
and is active.
For example, for a single float system,
“Fill Tank”
will start the engine if the Float 1 switched input is
inactive (open).
“Empty Tank” will start the engine if
the Float 1 switched input is active (closed). Refer to
the
section of the manual in
the Application section.
Single / Dual Floats mode is set by the
“Float
AutoStart
” setting in the Application > Function menu.
Tank Maximum
Sub menu
-----
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...