Name
Range
Default Settings
Description
Speed Settings >
Tooth Count
1 ~ 600
110
(only applies when Signal Source is set to
Mag Pickup) Number of teeth on the
flywheel.
If the number of teeth is unknown, the
following formula can be used. A
multimeter must be used to measure the
AC frequency (Frequency-In-Hz below)
from the magnetic pickup. The speed
(Speed-In-RPM below) must be known.
Tooth-Count = (Frequency-In-Hz * 60) /
Speed-In-RPM
Setpoints > Low
Warn (Under Speed
Warning)
20 ~ 99%
90%
Reading at which a warning occurs.
Setpoints > Low Fail
(Under Speed
Failure)
20 ~ 99%
85%
Reading at which a failure occurs.
Setpoints > High
Warn (Over Speed
Warning)
101 ~ 150%
110%
Reading at which a warning occurs.
Setpoints > High
Fail (Over Speed
Failure)
101 ~ 150%
115%
A over speed failure is triggered if the
speed is above this threshold for 4
seconds.
RPM Control > Min
Speed
500 ~ 4000 RPM
in 1 RPM
increments
600 RPM
Front Panel Speed Control Settings. See
the
more information on these settings.
RPM Control > Max
Speed
500 ~ 4000 RPM
in 1 RPM
increments
2000 RPM
RPM Control >
Speed Bias
0 to 600 RPM
in 1 RPM
increments
30 RPM
RPM Control >
TSC1 RPM/s
Disabled
10 to 300 RPM
in 10 RPM
increments
200 RPM
RPM Display
Blank
AC Hertz
Aux Sensor 1
Aux Sensor 2
AC Hertz
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...