Setting
Value
Mode Select
Start on Low
Mode Settings > Active Time
40 min
Mode Settings > Start Level
10.5 V
Mode Settings > Stop Level
1
Disabled
1
Stop Level needs to be disabled when the engine is running because the battery voltage will equal the
alternator charging voltage. Having this disabled will force the engine to run for the entire duration of the active
time.
The following chart shows the connection between a battery bank and time. At approximately 80 minutes time,
the voltage falls below the 10.5 V start threshold, causing the engine to start. The engine runs for the 40 minutes
of active time, regardless of the voltage reading, and then shuts down.
5.5.6.3
Output on High Example
In this example, a sensor is monitoring the temperature of an engine. If the temperature rises above 325 °F, a
fan will turn on to cool the engine. Once the temperature drops to below 200 °F, the fan will turn off.
Relevant Settings (Auxiliary Sensor)
Setting
Value
Signal Source
Same as Engine Temperature
Display
Disable (if enabled, controller will display Engine Temperature twice)
Sensor Type
Same as Engine Temperature
Sender Table Name
Engine Temp.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...