DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
90
9M02-9249-A001-EN
Revision A
Name
Range
Default
Description
Auto Idle Link
5.6.1.1
Preheat Mode
The controller has the ability to control the length of the preheat time through three different methods. The
following table describes each method.
Preheat Mode Settings (under Timers > Engine Logic menu)
Mode
Description
Preheat Timer
This mode uses the Preheat Time setting in the Engine Logic menu.
Switched Input
This mode uses a switched input set to
‘ECM Preheat’ to determine when to exit
preheat.
The preheat time (in
) must be set to a minimum of 5 seconds for this
input to work. If the switched input is or becomes active when the preheat timer is
counting down, the controller displays
‘ECM Preheating’ on the screen after the
preheat counter has finished its countdown. Cranking begins when the
‘ECM Preheat’
switched input is no longer active.
J1939
This mode uses commands sent from the ECM over J1939 to decide when to exit
preheat.
CAUTION
DURING PREHEAT, THE GLOWPLUG SWITCHED OUTPUT IS ON (IT NEEDS TO BE SET TO A
SWITCHED OUTPUT
– SEE
ATTENTION
PENDANT LE PRECHAUFFAGE, LA SORTIE COMMUTEE GLOWPLUG (VOYANT DE
PRECHAUFFAGE) EST ACTIVEE (ELLE DOIT ETRE PARAMETREE EN SORTIE COMMUTEE -
VOIR
SWITCHED OUTPUTS SWITCHED OUTPUTS
5.6.1.2
False Restart
The false restart feature is used to monitor and recover from unsuccessful crank attempts where the speed did
go above the crank disconnect and the controller is in the Run Mode. For example, the engine might have stalled
shortly after cranking.
False Restart Settings (under Timers > Engine Logic)
Name
Range
Default
Description
False Restart
(Restart on False
Start)
Enable
Disable
Disable
Determines if the controller will monitor for
false starts and attempt a restart.
Controller will only attempt restarting the
engine as many times as determined by
Crank Attempts.
!
!
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...