Mode Settings >
Bypass Time
0 ~ 90 s
in 1 s increments
-----
The amount of time to ignore the sensor input
after the desired active mode is first entered.
Once triggered, the bypass time does not apply
again until the device resets (for example,
transitioning from Run to the Off or Auto state) or
on power-up.
Mode Settings >
Run Time
Disable
1 ~ 6000 min*
in 1 min increments
-----
(Only applies if Func. Select is
not
set to Fault
Monitor) The amount of time to turn on the
auxiliary switched output or run the controller
before turning off the output or shutting down the
controller.
If the Run Time is disabled, then the start/output is
held until the Stop Level is reached (if enabled) or
until the controller is reset or powered down or, in
the case of Start on Low / Start on High, until the
user presses the OFF button.
Note that the run time is not exact. Up to 10
seconds may be added to the beginning of the run
time counter and up to 4 seconds to the end. The
run time begins when a start request is received
so crank time, preheat time, etc., are included in
the Run Time.
Mode Settings >
Start Level
Disable
Temperature
:
32 ~ 999 °F
in 1 °F increments
Pressure
:
1 ~ 6000 PSI
in 1 PSI increments
Level
:
1 ~ 99%
in 1% increments
Voltage
:
0.1 ~ 99.9 V
in 0.1 V increments
Current
:
1 ~ 999 A
in 1 A increments
-----
(Only applies if Func. Select is
not
set to Fault
Monitor) The level at which the auxiliary switched
output turns on or the engine starts.
If this is set to Disable, the Auxiliary Sensor action
defined in Func. Select is disabled. The Auxiliary
Sensor becomes display only (unless Func.
Select is set to Fault Monitor).
Mode Settings >
Stop Level
(Only applies if Func. Select is
not
set to Fault
Monitor) The level at which the auxiliary switched
input turns off or the engine is stopped.
If Stop Level is disabled, the start/output condition
is maintained until the Run Time expires (if
enabled) or until the controller is reset or powered
down or, in the case of a start, until the user
presses the OFF button.
Setpoints > Low
Warning
(Only applies if Func. Select is set to Fault
Monitor) Reading at which a warning occurs.
Setpoints > Low
Failure
(Only applies if Func. Select is set to Fault
Monitor) Reading at which a failure occurs.
Setpoints > High
Warning
(Only applies if Func. Select is set to Fault
Monitor.) Reading at which a warning occurs.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...