Event Name
Event Type
Description
Under Voltage
Warning
The generator AC voltage has fallen below the under voltage warning
setpoint set under AC Monitor > Genset Voltage. Possible issue with
the voltage regulator or speed governor on the engine.
Under Speed
Warning
The generator speed has fallen below the under speed warning
setpoint set under Sensors > Engine Speed.
Over Speed
Warning
The generator speed has risen above the over speed warning setpoint
set under Sensors > Engine Speed.
High Engine Temp
Warning
The engine temperature has risen above the high engine temperature
warning under Sensors > Engine Temp.
Low Oil Pressure
Warning
The oil pressure has fallen below the low oil pressure warning setpoint
under Sensor > Oil Pressure.
Low Fuel Level
Warning
The fuel level has fallen below the low fuel level warning setpoint
under Sensors > Fuel Level.
False Restart
Warning
After going into the Run Mode, the controller has determined that the
engine has not started after all and will attempt to do another crank
attempt. The fault restart feature under Engine Logic > Timers has to
be enabled.
Breaker Tripped
Warning
The
“Breaker Trip” switched output has been activated. This output is
used to control the generator breaker.
Over Current
Warning
The generator AC current has risen above the over current warning
setpoint under AC Monitor > O.C. Protection > Basic Alarm.
Fuel In Basin
Warning
The
“fuel in basin” switched input has been triggered. This indicates
there has been a leak in the fuel tank.
Low Battery
Warning
The main starter battery (the battery from which the controller is
powered) voltage has fallen below the low battery warning setpoint
under Sensors > Battery.
High Battery
Warning
The main starter battery (the battery from which the controller is
powered) voltage has risen above the high battery warning setpoint
under Sensors > Battery.
Low Engine Temp
Warning
The engine temperature has fallen below the low engine temperature
warning setpoint set under Sensors > Engine Temp. > Setpoints.
Battle Running
Warning
The
“Battle Mode” switched input has been triggered. The controller
will not shut down on any failures. All failures will be ignored.
Under Frequency
Warning
The generator AC frequency has fallen below the under frequency
warning setpoint set under AC Monitor > Genset Freq. > Setpoints.
Over Frequency
Warning
The generator AC frequency has risen above the over frequency
warning setpoint set under AC Monitor > Genset Freq. > Setpoints.
Load Imbalance
Warning
The generator load is imbalanced between the A, B, and C phases.
This has to be enabled under AC Monitor > O.C. Protection >
Imbalance Mode.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...