Configurable
Failure 2
Configurable
The settings under Timers > Trigger Delays > Config Inputs and
Timers > Trigger Delays > Config Fail 3 can be set to control the
amount of time the input has to be active in order to trigger.
Configurable
Failure 3
Configurable
Air Press. Fail (Air
Pressure Failure)
Cranking
Controller displays
‘Low Air Pressure’ and shuts down engine
when active.
Hyd Pres. Fail
(Low Hydraulic
Pressure Failure)
Cranking
Controller displays
‘Hydraulic Pressure Failure’ and shuts down
engine when active.
Oil Pres Warn (Low
Oil Pressure
Warning)
Running
Controller displays
‘Oil Pressure Warning’ when active.
Cool. Lvl Fail (Low
Coolant Level
Failure)
Global
Controller displays
‘Low Coolant Lvl’ and shuts down engine
when active.
High Fuel Warning
Global
Controller displays
‘High Fuel Level’ warning when active.
Lamp Test
Global
Controller performs lamp test when active. If the controller is in
the Failure Mode, the LED will remain red. The only indication
that the lamp test is active is the LED indicator will alternate
between the green and red colors. The LED goes back to its
original state when the switched input is no longer active.
Fuel In Basin
Global
Controller displays
‘Fuel In Basin’ warning when active.
Battle Mode
After Cranking
Controller ignores all warnings and failures when active.
Displays
‘Battle Running’ when active. If a failure occurs during
Battle Mode, it is
‘latched’ and the engine will shut down on
failure when the controller leaves Battle Mode.
Start Inhibit
Global
Controller ignores all start commands, and the engine cannot
start when active. Once Start Inhibit becomes inactive, starting is
enabled again. If the engine is running, activating this input will
shut down the engine and place the controller in Auto Mode.
RPM Switch
(Primary RPM /
60 Hz -
Secondary RPM
/ 50 Hz Select)
Auto
Used for changing between Primary and Secondary RPM for an
engine or 50 Hz / 60 Hz for a generator. See
ECM Preheat
(ECM Preheat
Signal)
Cranking (during
the Preheat
countdown only)
Controls preheating using a switched input. See Switched Input
in the
section.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...