DynaGen
TM
TOUGH Series
TM
TE410 - EN
User Manual
61
9M02-9249-A001-EN
Revision A
Name
Active Mode
Description
Off Mode (Not In
Auto)
Off
Active when the controller is in the Off Mode.
Idle Mode
Idle Mode
Active when the controller is in Idle Mode. For example,
when the idle switched input is active or during warmup
and cooldown if warmup idle and cooldown idle settings
under Timers > Engine Logic are enabled.
Battle Mode
Battle Mode
Active when Battle Mode switched input is active.
System OK
(System Ready)
Auto, Run
Active when the controller is in the Auto and Run Modes
and no warnings or failures are present.
Delay to Start
Delay to Start Timer
Active when the Delay to Start timer is active.
Glowplug
Preheat, Midheat,
Postheat
Active during the Preheat, Midheat and Postheat timers.
Warmup
Warmup Timer
Active in Run Mode after Warmup Timer has expired. Is not
active in the cooling down state or other states. Typically
used to apply load to the engine only after it has warmed
up and to remove the load on cooldown.
Cooldown
Cooldown Timer
Active when Cooldown Timer is active.
Engine Running
Running
Active after crank success.
Exercising
Exercise Timer
Active during the engine exercising cycle.
Batt. Recharge
(Battery Recharge)
Battery Recharge Timer
Active during the battery recharge cycle.
Maintenance
(Maintenance
Required)
Global
Active when Maintenance timer has expired. If the timer
has expired when the controller is in the Run Mode, the
output does not turn on until the controller enters the Off or
Auto Mode. See the
section.
LowBat InCrank
(Low Battery
During Cranking)
Cranking
Active when Low Battery During Cranking warning is
displayed.
Aux Sensor 1
Auxiliary Settings
Dependent
Active dependent upon settings in the
section.
Aux Sensor 2
Aux Sensor 3
Aux Sensor 4
Force Regen
User Controlled
When user triggers a Force Regeneration, output is active
for 20 seconds then switches off.
Regen Inhibit
User Controlled
When user triggers a Regeneration Inhibit, output is active
for 20 seconds then switches off.
Common Failure
Any Failure
Active when any failure occurs.
Содержание DYNAGEN TOUGH Series TE410
Страница 1: ...TOUGH SeriesTM TE410 User Manual ...
Страница 14: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 14 9M02 9249 A001 EN Revision A 2 3 Wiring Harness ...
Страница 15: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 15 9M02 9249 A001 EN Revision A 2 4 Typical Wiring Diagram ...
Страница 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Страница 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Страница 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...