Installation Manual
Comms Programming
9-16
Bosch Security Systems 07/14 BLCC610I
Comms > Reporting >
Burg Report Delay
MENU 5-4-6
(*** System Wide Parameter ***)
0 0 0
Seconds
This menu programs how long the panel will delay
reporting Burglary alarm reports. Only burglary (non-
fire) zones that have been programmed for Delay Report
in MENU 3-1-7 — Report Option will follow the Burglary
Report Delay time.
1)
Press [MENU] + [5] + [4] + [6]. The keypad will
display the current burglary report delay time.
Burg Report Delay
000 Seconds
Press 0-9 OK to SAVE
2)
Using the numeric keys, enter the new report delay
time then press [OK] to save and exit or press
[MENU] to exit without saving. Valid entires are 0
to 255 seconds
Comms > Reporting >
Fire Report Delay
MENU 5-4-7
(*** System Wide Parameter ***)
0 0 0
Seconds
This menu programs how long the panel will delay
reporting fire zone alarm reports. Only fire zones that
have been programmed for Delay Report in MENU 3-1-7
— Report Option will follow the Fire Report Delay time.
1)
Press [MENU] + [5] + [4] + [7]. The keypad will
display the current Fire Report Delay time.
Fire Report Delay
000 Seconds
Press 0-9 OK to SAVE
2)
Using the numeric keys, enter the new report delay
time then press [OK] to save and exit or press
[MENU] to exit without saving. Valid entires are 0
to 255 seconds.
M YA L A R M
Comms > MyAlarm >
IP Address
MENU 5-5-0
1
Digits
12
0 0 0
0 0 0
0 0 0
0 0 0
This menu programs the 12 digit MyAlarm IP Address.
i
Note
MENU 5-5-0 should be left at the factory default
settings unless you are advised otherwise by the
manufacturer.
1)
Press [MENU] + [5] + [5] + [0]. Use the arrow keys to
select the IP address to program, then press the
[OK] key. The keypad will display the current IP
address.
Primary IP Address
000000000000
Press 0-9 OK to SAVE
2)
Using the numeric keys, enter the IP address
required, then press [OK] to save and exit, or press
[MENU] to exit without saving.
Comms > MyAlarm >
IP Port
MENU 5-5-1
0 7 7 0 3
This menu programs the 5 digit MyAlarm Port number.
Range must be programmed within 0 to 65535.
i
Note
MENU 5-5-1 should be left at the factory default
settings unless you are advised otherwise by the
manufacturer.
1)
Enter [5] + [5] + [1] + [OK]. Use the arrow keys to
select the IP port to program, then press the [OK]
key. The keypad will display the current MyAlarm
Port number.
Primary IP Port
07703
Press 0-9 OK to SAVE
2)
Using the numeric keys, enter the IP address
required, then press [OK] to save and exit, or press
[MENU] to exit without saving.