Solution 6000
Installation Manual
Programming Overview
4-4
Bosch Security Systems 07/14 BLCC610I
ZO N E A R R AY
The feature allows you to view the condition of all zones
on the panel in banks of 16 zones at a time. From the
installer programing mode press MENU 3-0-1 to access
the zone array.
Use the [
] and [
] arrow keys to scroll up and down the
zone banks and press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current zone status.
N
= NORMAL
S
= SHORTED
A
= ALARM
T
= TAMPER
-
= DISABLED
0000000001111111
1234567890123456
NSA-ANAT--------
Press
OK or MENU
In the above example screen,
N
= Zone 01 and 06 are Normal (Sealed)
S
= Zone 02 is Shorted
A
= Zone 03,05,07 are in Alarm (Unsealed)
T
= Zone 08 is in Tamper Alarm (Unsealed)
-
= Zone 04, 09-16 are Disabled (Unused)
O U T P U T A R R AY
This feature allows you to view output status in groups of
16. From the installer programing mode press MENU 4-0-
2 to access the output array.
Use the [
] and [
] arrow keys to scroll up and down the
output banks and press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current zone status.
N
= NORMAL - Off Condition
T
= TRIGGERED - On Condition
F
= FAULT - Overload Condition
-
= DISABLED
1)
Enter [MENU] + [4] + [0] + [2] and use the up and
down arrows to select the output group to view.
2)
Use the up and down arrows at any time to move to
a new group. The keypad will display the following
output array information for outputs 1 to 16.
0000000001111111
1234567890123456
NNNNN---TF------
Press
OK or MENU
In the above example screen,
N
= Outputs 01 to 05 are Normal (Off)
F
= Output 10 has a Fault (Overload)
T
= Output 09 is Triggered (On)
-
= Outputs 05 to 08 and Outputs 11 to 16 are
Disabled or Not Available
D O O R A R R AY
This feature allows you to view door status in groups of 16.
From the installer programing mode press MENU 4-0-4 to
access the door array.
Press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current door status.
L
= Door Locked
U
= Door Unlocked
O
= Override
-
= Disabled or Not Available
0000000001111111
1234567890123456
LLLLL---UUUUO---
Press
OK or MENU
In the above example screen,
L
= Doors 01 to 05 are Locked
O
= Door 13 has a Override condition
U
= Doors 09 to 12 area Unlocked
-
= Doors 06 to 08 and Doors 14 to 16 are Disabled or
Not Available
T E S T I N G T H E S YS T E M
You will need to be in programming mode before
accessing the test functions listed below.
Walk Test
Use the walk test command MENU 3-9-0 to test and verify
that all zones work correctly.
External Audible Test
Use MENU 4-9-0 to test and verify that all horn speakers
operate. This test will sound the horn speaker for two
seconds.
Internal Audible Test
Use MENU 4-9-1 to test and verify that all 12 VDC sirens
operate. This test will sound the siren for two seconds.
Strobe Test
Use MENU 4-9-2 to test and verify that the strobe operates.
This test will turn on the strobe until you manually stop
the test.
Battery Test
Use MENU 7-9-1 to test the back-up battery that is
connected to the control panel.
Communication Test
Use MENU 5-9-0 to test the telephone reporting capability
of the control panel. You can also activate a communication
test by holding down the Test / Mail key on the keypad.