Solution 6000
Installation Manual
System Programming
11-8
Bosch Security Systems 07/14 BLCC610I
System > Power >
Battery Options
MENU 7-3-1
1
Display Battery Fail
Y
2
Report Battery Fail
Y
3
Battery Test On Arming
Y
4
OK To Arm Low Battery
Y
5
Reserved
N
6
Reserved
N
7
Reserved
N
8
Reserved
N
(*** System Wide Parameter ***)
This menu option allows you to configure the standby
Battery system options. The system is constantly
monitoring the battery condition with a dynamic battery
test carried out every 4 hours.
1)
Press [MENU] + [7] + [3] + [1]. The keypad will
display the current Battery Options.
Display Battery Fail
Report Battery Fail
Battery Test On Arming
Press
OK ON OFF MENU
2)
Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable.
3)
Repeat Step 2 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Display Battery Fail
Setting this option will cause the keypad to display
a Trouble condition when the panel detects that the
standby battery is disconnected or that its voltage is low.
The trouble condition will clear as soon as the panel has
measured the battery voltage is 12.5 volts or greater.
Report Battery Fail
Setting this option will cause the panel to send a Low
Battery report to the base station when it measures
the battery voltage has dropped below 11.5 volts. A
Low Battery Restore report will be sent when the panel
detects that the battery voltage is above 12.5 volts.
If the panel fails to detect the battery, or if it measures
the battery voltage below 10.2 volts, then a Battery Test
Failed report will be sent. A Battery Test restore will be
sent when the battery is re-connected or replaced.
Battery Test On Arming
Setting this option will cause the panel to perform an
additional dynamic battery test each time Area 1 is
armed All On.
OK To Arm Low Battery
Setting this option will allow the system to be armed
even though the panel currently has a low battery
condition.
When this option is disabled, the panel will not arm
if there is a low battery condition or if the battery is
missing. The user will be notified of the system trouble
on the keypad and they will need to have the fault
rectified before the system or area can be armed.
System > Power >
Fuse Options
MENU 7-3-2
1
Display COMM+ O/Load
Y
2
Report COMM+ O/Load
Y
3
D12v O/Load
Y
4
12v O/Load
Y
5
Display LAN O/Load
Y
6
Report LAN O/Load
Y
7
Reserved
N
8
Reserved
N
(*** System Wide Parameter ***)
This menu option allows you to configure the Fuse related
system options.
1)
Press [MENU] + [7] + [3] + [2]. The keypad will
display the current Fuse Options.
Display COMM+ O/Load
Report COMM+ O/Load
D12v O/Load
Press
OK ON OFF MENU
2)
Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable.
3)
Repeat Step 2 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Display COMM+ O/Load
Setting this option allows the keypad to display a system
trouble message when the current load on the COMM +
terminal exceeds its maximum rating of 3 Amps.
Report COMM+ O/Load
Setting this option will cause the panel to send an
Overcurrent Trouble report to the base station when
the current load on the COMM + terminal exceeds its
maximum rating of 3 Amps.
Содержание SOLUTION 6000
Страница 1: ...Solution 6000 Security System Installation Guide EN Security Systems ...
Страница 42: ...Solution 6000 Installation Manual Programming Overview 4 12 Bosch Security Systems 07 14 BLCC610I ...
Страница 82: ...Solution 6000 Installation Manual Input Programming 7 16 Bosch Security Systems 07 14 BLCC610I ...