Solution 6000
Installation Manual
Device Programming
10-9
Bosch Security Systems 07/14 BLCC610I
2)
Use the numeric keys to program the number of
seconds the keypad will be locked out for. Valid
entries are 0 - 255, 0 = No Lockout.
3)
Press [OK] to save and exit, else press [MENU] to
exit without saving.
R F R E C E I V E R O P T I O N S
Devices > RF Devices >
Receiver Options
MENU 6-2-0
1
Display RF Rcvr Trouble
Y
2
Alarm RF Rcvr Tamper
Y
3
Report RF Rcvr Tamper
Y
4
Alarm RF Rcvr Jamming
N
5
Report RF Rcvr Jamming
N
6
Alarm Rcvr Comms Fail
Y
7
Report Rcvr Comm Fail
Y
8
Reserved
N
This menu option allows you to configure the various RF
receiver functions. Only one RF reciever can be fitted per
panel.
1)
Press [MENU] + [6] + [2] + [0]. The keypad will
display the current receiver options.
Display RF Rcvr Trouble
Alarm RF Rcvr Tamper
Report RF Rcvr Tamper
Press
OK ON OFF MENU
2)
Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable.
3)
Repeat Step 2 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Display RF Rcvr Trouble
Setting this option allows the panel to display a trouble
condition on the keypad when an RF receiver fail
condition occurs.
Alarm RF Rcvr Tamper
Setting this option allows the panel to trigger an alarm
when the RF receiver tamper circuit is tripped.
Report RF Rcvr Tamper
Setting this option allows the panel to send an RF
Receiver Tamper report to the the base station when the
RF receiver tamper circuit is tripped. A restore report will
be sent when the tamper circuit is resealled.
Alarm RF Rcvr Jamming
Setting this option allows the panel to sound an
alarm when the RF Receiver detects a jamming signal.
This signal may not be provided by all compatible RF
Receivers.
Report RF Rcvr Jamming
Setting this option allows the panel to send an RF
Receiver Jam report to the base station when the RF
Receiver detects a jamming signal. A restore report will
be sent as soon as the jamming signal stops.
Alarm Rcvr Comm Fail
Setting this option allows the panel to sound an alarm
when it is unable to communicate with the RF Receiver.
Report Rcvr Comm Fail
Setting this option allows the panel to send an RF
Receiver Comms Fail report to the base station when the
panel is unable to communicate with the RF Receiver. A
restore report will be sent as soon as communication is
restored between the panel and the RF receiver.
Device > RF Devices >
Supervision Time
MENU 6-2-1
(*** System Wide Parameter ***)
0
2 4
HOURS
This menu sets the global RF supervision time for all RF
devices connected to the system.
RF transmitters (sensor devices) will send a supervisory
test signal approximately once every hour. The RF receiver
expects to receive this supervisory signal from every
transmitting device within the supervision time period.
The panel will send a Missing report to the base station for
any RF device that fails to report within the supervision
time.
1)
Press [MENU] + [6] + [2] + [1]. The keypad will
display the current RF supervision time.
Supervision Time
024 Hours
Press 0-9 OK to SAVE
2)
Using the numeric keys, enter the number of hours
for the RF supervision time. Valid times are 0 - 255
hours, 0 = No Supervision.
3)
Press [OK] to save and exit or press [MENU] to exit
without saving.