Coding DOUT 2
–
Coding DOUT 6
=
High active
5.3.
Configurable status signals
Requirements
<Additional inputs> or additional <Parallel interface>.
The status signals described here are collective signals of various other signals. For
configuration, the contained signals can be selected from a list and activated ( ) or
deactivated ( ) individually.
The status signals can either be assigned to a digital output (output contact) or to
an indication light (LED).
For detailed information on these signals, refer to
page 144, Fault indications and
chapter.
Configure status signals
Required user level:
Specialist (4)
or higher.
Device configuration M0053
Config. of signals M0860
Failure (configurable) M0879
Fault (Cfg) M0880
Warnings (Cfg) M0881
Not ready REMOTE (Cfg) M0882
A dot in the display indicated whether the signal is active or not.
Figure 29: Example
Black dot (
●
): Signal active
White dot (
○
): Signal not active
Activation/deactivation is switched on/off by push button
Ok
.
5.4.
Analogue signals (analogue outputs)
Conditions
The actuator is equipped with a position transmitter.
Characteristics
Depending on the actuator equipment, different signals, such as travel, torque or
output speed can be recorded and issued as continuous values, e.g. 4 to 20 mA.
Actuator controls are equipped with up to two analogue outputs, AOUT1 and AOUT2.
5.4.1.
Assignment of analogue output 1
Required user level:
AUMA (6)
.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal AOUT 1 M0131
Default value:
Actual position
Information
The signal range of the output (e.g. 0/4 – 20 mA) is set via a separate parameter
(
Signal range AOUT1 M0129
).
Setting values:
Not used
Analogue output 1 is not assigned.
Actual position
Position feedback of the valve position (actual position value E2)
Condition: Position transmitter installed in the actuator.
28
Actuator controls
Signals (output signals)
ACV 01.2/ACVExC 01.2 Profibus DP