●
in selector switch position Remote control (REMOTE):
-
Via fieldbus, Reset command, byte 1 bit 3 of output data if fieldbus is the
active command source.
-
Or via a digital input (I/O interface) with RESET command if a digital input
is configured for
RESET
signal and the I/O interface is the active command
source.
In case of operation from an intermediate position, reaction monitoring will only be
performed if the actuator is equipped with position feedback function.
Activate switching off for reaction time error
Required user level:
Specialist (4)
or higher.
Customer settings M0041
Reaction monitoring M0632
Actuator behaviour M0633
Default value:
No cut-off
Setting values:
No cut-off
The reaction monitoring only issues a warning.
Cut-off
The reaction monitoring issues a fault signal, the actuator is stopped.
Set reaction time
Customer settings M0041
Reaction monitoring M0632
Reaction time M0634
Default value:
15.0 s
Setting range:
15.0 ... 300.0
seconds (0 seconds up to 5 minutes)
10.6.
Motion detector
Requirements
Position transmitter in the actuator.
Characteristics
The motion detector checks whether the actuator moves even without operation
command (e.g. in manual operation or if there is no self-retaining).
Controls identify motion if the actuator moves more than the pre-set travel difference
within the predefined recording time. Controls signal:
Output drive rotates
Information
Parameters for motion detection have a direct impact on reaction monitoring.
10.6.1.
Activate motion detector
Required user level:
Specialist (4)
or higher.
Customer settings M0041
Motion detector M0676
Motion detector M0675
Default value:
Function active
Setting values:
Function not active
Monitoring is deactivated.
Function active
Monitoring is activated.
10.6.2.
Detection time dt
Required user level:
Specialist (4)
or higher.
Customer settings M0041
Motion detector M0676
Detect. time dt M0677
Detect. time dt (MWG) M0681
110
Actuator controls
Monitoring functions
ACV 01.2/ACVExC 01.2 Profibus DP