Speed internal 4 M1933
Default values:
45 rpm
Setting range: The adjustable speed range is indicated on the actuator name plate.
8.1.3.
Speed range for analogue input: set
This setting is only effective if one of the speed sources is either set to
Analogue
input
or
Fieldbus
.
Customer settings M0041
Speed functions M1699
Speed rem. min. M1936
Speed rem. max M1937
Default values:
Speed rem. min.
=
6 rpm
(
≙
0/4 mA)
Speed rem. max
=
60 rpm
(
≙
20 mA)
Setting values:
Speed rem. min.
=
6 ... 240 rpm
(revolutions/minute)
Speed rem. max
=
6 ... 240 rpm
(revolutions/minute)
The adjustable speed range is indicated on the actuator name plate.
8.1.4.
Time for speed increase and time for speed reduction at pivot points
The transition time from a low to a high speed can be set. This applies e.g. to speed
transition within pivot point range. Refer to <Speed profile>.
Figure 33: Example of time for speed increase
n
Output speed
P
Pivot point
t
Operating time (travel)
t
↗
Time for speed increase
Set time for speed increase
Customer settings M0041
Speed functions M1699
Time speed incr. M1769
Default values:
Time speed incr.
=
0.2 s
(seconds) from lower to higher speed
Setting ranges:
Time speed incr.
=
0.1 – 10.0
(seconds)