Configuration of digital inputs
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Use input DIN4 for signal
Bypass Sync In
:
Use input DIN6 for signal
EMERGENCY
:
Setting values:
●
Signal DIN 5 M0122
=
By-pass Sync In
(wiring diagram designation:
BYPASS SYNC IN
)
●
Signal DIN 6 M0121
=
EMERGENCY
(wiring diagram designation:
NOT/EMERGENCY
)
Information
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g.
Coding DIN 6 M0128
), the input is either
High active
or
Low active
. Default
setting is
High active
.
Configuration of digital output
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Example
Use output DOUT6 for signal
Bypass Sync Out
:
Parameters:
Signal DOUT 6 M0111
Setting value:
Bypass Sync Out
(wiring diagram designation:
BYPASS SYNC
OUT
)
8.14.1.
By-pass function: activate
Required user level:
Specialist (4)
or higher.
Device configuration M0053
Application functions M0178
Activation M0212
By-pass function M0941
Default value:
Function not active
Setting values:
Function not active
Bypass function deactivated.
Function active
Bypass function activated.
8.14.2.
By-pass application: configure
The actuators for the two MOVs (valves) have to be configured according to their
application (main or by-pass valve).
Customer settings M0041
By-pass function M0942
By-pass application M0943
Default value:
Main valve
Setting values:
Main valve
Actuator for main valve.
By-pass valve
Actuator for by-pass valve.
80
Actuator controls
Application functions
ACV 01.2/ACVExC 01.2 Profibus DP