8-6
ADS
Manual
Positive Wire
Negative Wire
I/O TERMINAL BLOCK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1
2
1
2
I1
I2
R1
R2
+ -
+ -
+ -
+ -
NC
4-20 mA
Analogue
Outputs
4-20 mA
Analogue
Inputs
Digital
(Switch)
Inputs
Digital
(Relay)
Outputs
ANALOG INPUT TERMINALS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Connecting the
positive
and negative wires from the third-party device to
Terminals
1
and
2
(analog input terminals) on the I/O terminal block
Connect the other ends of the positive and negative wires
to the third-party device based on the vendor’s
specifications.
Close and latch the door to the XIO.
4.
Restore power to the customer’s instrument or device and the
ADS XIO.
5.
Verify that adding the ADS equipment will not add too much
load
to the analog signal
loop
. The XIO input adds 22 ohms to
the loop. If too much load is added, the signal will
clip
and
cause the data to flat line at a lower level than the true peak,
which will result in understated peak levels or flows. If only
one device is connected to the analog signal, sufficient current
is probably available to drive the XIO input. If more than two
devices are attached to the analog signal loop, ADS strongly
recommends load testing the loop.
Содержание Intrinsically-Safe TRITON+
Страница 19: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Страница 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Страница 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Страница 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Страница 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...
Страница 34: ...Introduction 1 27 Activate Monitor Qstart software Run Diagnostics and Perform Confirmations Qstart software ...
Страница 49: ...2 12 ADS TRITON Manual ExPAC XBUS ...
Страница 159: ...External Power 5 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 171: ...External Power 5 21 POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS Wires exiting DC output terminal on power supply ...
Страница 231: ...6 44 ADS TRITON Manual Editing the Smart Ultrasonic Depth Sensor Device Edit Smart Depth 1 Parameters dialog ...