Configuration and Activation 6-69
Min Value
Input the minimum value for the incoming analog
signal which will be used to scale the data values. This value
represents the weakest signal corresponding to the incoming
4mA signal. For example, enter the value corresponding to the
lowest depth reading for a DEPTH_A1 input.
Max Value
Input the maximum value for the incoming
analog signal which will be used to scale the data values. This
value represents the strongest signal corresponding to the
incoming 20mA signal. For example, enter the value
corresponding to the highest depth reading for a depth
(DEPTH_A1) input.
The monitor temporarily stores all incoming analog input readings
which occur between each monitor storage interval.
Average
Select this checkbox to store the analog input signal
value as an average of all analog input readings since the last
monitor storage interval. If this checkbox is not selected, the
stored analog input value (when the
Store Data
checkbox is
selected) will be the most recent analog input
reading.
Checkbox is selected by default.
Store Data
Select this checkbox when to store the analog
input to the monitor memory at the monitor’s storage
interval. (This value is
averaged
or
actual
value depending on
whether the
Average
checkbox is selected.)
Checkbox is
selected by default.
Store Min
Choose this checkbox to store the lowest analog
input reading which occurs within each sample interval as the
MIN_A1 data entity.
Checkbox is selected by default.
Store Max
Choose this checkbox to store the highest analog
input reading which occurs within each sample interval as the
MAX_A1 data entity.
Checkbox is selected by default.
Store Avg
Select this checkbox to store an averaged value of
the analog input signal as the AVG_A1 data entity.
Checkbox is
selected by default.
Содержание Intrinsically-Safe TRITON+
Страница 19: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Страница 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Страница 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Страница 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Страница 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...
Страница 34: ...Introduction 1 27 Activate Monitor Qstart software Run Diagnostics and Perform Confirmations Qstart software ...
Страница 49: ...2 12 ADS TRITON Manual ExPAC XBUS ...
Страница 159: ...External Power 5 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 171: ...External Power 5 21 POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS Wires exiting DC output terminal on power supply ...
Страница 231: ...6 44 ADS TRITON Manual Editing the Smart Ultrasonic Depth Sensor Device Edit Smart Depth 1 Parameters dialog ...