6-10 ADS Manual
Enter the slave address number in the
ID
field to be used
when facilitating communication between the
/ExPAC/XBUS and the third-party system (e.g.,
a SCADA system, RTU, or process control system).
Choose a number from 1 to 254, excluding the numbers 1,
58, and 97. For installations involving the Telog Ru-33,
ADS recommends using 55 as the slave ID.
Enter the amount of time, in milliseconds, following a
request you want the monitor to wait before returning the
requested data to the third-party system in the
Delay
Response
field. (This field typically does not need
editing.)
Click on the
OK
button.
10.
Select the
Save
button to save the current parameters on the
dialog to the local directory or network.
11.
Continue to enter the monitoring point information and assign
and edit the devices.
Configure the Monitoring Point(s)
The second step in configuring a monitor is entering the monitoring
point information. This involves designating the pipe
characteristics at the monitoring point and assigning and editing the
devices corresponding to the monitoring point.
The monitoring point represents the physical location at which the
sensors are installed in the pipe or channel. A monitor location can
support up to two monitoring points, and the settings must be
designated for each monitoring point.
Enter the information for each monitoring point in the following
way:
1.
Select the type or shape of the pipe or channel in which the
sensors are installed from the
Type
drop-down list on the ADS
Qstart
dialog.
Содержание Intrinsically-Safe TRITON+
Страница 19: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Страница 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Страница 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Страница 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Страница 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...
Страница 34: ...Introduction 1 27 Activate Monitor Qstart software Run Diagnostics and Perform Confirmations Qstart software ...
Страница 49: ...2 12 ADS TRITON Manual ExPAC XBUS ...
Страница 159: ...External Power 5 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 171: ...External Power 5 21 POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS Wires exiting DC output terminal on power supply ...
Страница 231: ...6 44 ADS TRITON Manual Editing the Smart Ultrasonic Depth Sensor Device Edit Smart Depth 1 Parameters dialog ...