6-58 ADS Manual
Depth Alarms
High Threshold
Enter the flow depth at which you want the
monitor to contact the
IntelliServe
system to initiate an alarm.
Typically, this value is set to a height slightly below,
equivalent to, or exceeding the pipe height to ensure
notification occurs when the pipe is full or surcharge conditions
exist.
High-High Threshold
Enter a second, higher flow depth at
which you want the monitor to contact the
IntelliServe
system
to initiate an alarm. This value must be zero when this feature
is not in use or greater than the value entered for the
High
Threshold
when it is in use. ADS recommends setting this
value at least
two
inches
higher than the value for designated
for the
High Threshold
.
Unidepth Averaging
Readings to Average
Select the number of consecutive
Unidepth
readings you want the monitor to average to minimize
the impact of erroneous readings on the data.
Store Data
Select this checkbox to save the averaged
Unidepth data to the monitor memory.
Low Flow Alarm and Dual Data Rate
Note:
The Low Flow Alarm and Dual Data Rate
parameters are
read-only
fields through
Qstart
. However,
Qstart
will display the parameters designated for these
options when previously configured through the
Profile
software. Contact ADS customer support for more
information.
Cross Check Combo Sensors
Using the
Cross Check
function allows you to configure the
monitor to log an event each time two sensors assigned to the same
monitoring point measuring the same characteristic (i.e., flow depth
or velocity) of the flow return readings exhibiting a difference
Содержание Intrinsically-Safe TRITON+
Страница 19: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Страница 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Страница 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Страница 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Страница 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...
Страница 34: ...Introduction 1 27 Activate Monitor Qstart software Run Diagnostics and Perform Confirmations Qstart software ...
Страница 49: ...2 12 ADS TRITON Manual ExPAC XBUS ...
Страница 159: ...External Power 5 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 171: ...External Power 5 21 POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS Wires exiting DC output terminal on power supply ...
Страница 231: ...6 44 ADS TRITON Manual Editing the Smart Ultrasonic Depth Sensor Device Edit Smart Depth 1 Parameters dialog ...