9-4
ADS Manual
XBUS
CABLE GLAND
RS-485 CABLE
Running RS-485 cable through left cable gland in XBUS
3.
Loosen the screws on the terminal connector.
4.
Make sure the wires from the cable are stripped and separated.
5.
Insert the negative wire (
D-
) from the cable into the
negative
(
-)
terminal on the connector (
refer to the label adjacent to the
port
), and tighten the terminal screw.
6.
Insert the positive wire (
D+
) from the cable into the
positive
(
+
) terminal on the connector, and tighten the terminal screw.
7.
Insert the ground wire (
GND/SHL
) from the cable into the
ground
( ) terminal on the connector, and tighten the terminal
screw.
Содержание Intrinsically-Safe TRITON+
Страница 19: ...1 12 ADS TRITON Manual Control Drawing ...
Страница 25: ...1 18 ADS TRITON Manual First page of the TRITON ATEX Certificate ...
Страница 27: ...1 20 ADS TRITON Manual First page of the TRITON IECEx Certificate of Conformity ...
Страница 29: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 1 ...
Страница 30: ...Introduction 1 23 CSA Certificate of Compliance Page 2 ...
Страница 32: ...Introduction 1 25 Sample TRITON Declaration of Conformity Page 2 ...
Страница 34: ...Introduction 1 27 Activate Monitor Qstart software Run Diagnostics and Perform Confirmations Qstart software ...
Страница 49: ...2 12 ADS TRITON Manual ExPAC XBUS ...
Страница 159: ...External Power 5 9 Power supply firmly secured to the DIN rail Front view of power supply mounted to DIN rail ...
Страница 171: ...External Power 5 21 POWER SUPPLY DC OUTPUT TERMINAL CONNECTIONS Wires exiting DC output terminal on power supply ...
Страница 231: ...6 44 ADS TRITON Manual Editing the Smart Ultrasonic Depth Sensor Device Edit Smart Depth 1 Parameters dialog ...