CLOSE COMMAND
OR
SMBRREC (79)
OR
CCRBRF (50BF)
BU-TRIP
ZCVPSOF-TRIP
INHIBIT
UNSUCCL
TRBU
SMPPTRC (94)
AND
RESET LOCK-OUT
OR
OR
SESRSYN (25)
SOFTWARE
OR IO RESET
AUTOSTOP
MANENOK
MAN CLOSE
SMBRREC (79) CLOSE
CLLKOUT
RSTLKOUT
SETLKOUT
ANSI11000167_1_en.vsd
ANSI11000167 V1 EN
Figure 78:
Lock-out arranged with internal logic with manual closing going through
in IED
10.2.2.13
Automatic continuation of the reclosing sequence
SMBRREC (79) function can be programmed to proceed to the following reclosing shots
(if multiple shots are selected) even if start signals are not received from the protection
functions, but the breaker is still not closed. This is done by setting parameter
AutoCont
=
Enabled
and
tAutoContWait
to the required delay for the function to proceed without a
new start.
10.2.2.14
Thermal overload protection holding the auto-reclosing function back
If the input THOLHOLD (thermal overload protection holding reclosing back) is
activated, it will keep the reclosing function on a hold until it is reset. There may thus be
a considerable delay between start of Auto-Reclosing and reclosing command to the
circuit-breaker. An external logic limiting the time and sending an inhibit to the INHIBIT
input can be used. The input can also be used to set the Auto-Reclosing on hold for a longer
or shorter period.
10.2.3
Setting guidelines
10.2.3.1
Configuration
Use the PCM600 configuration tool to configure signals.
1MRK 511 286-UUS A
Section 10
Control
205
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...