The cursor is focused on the User identity field, so upon pressing the
key, one can
change the user name, by browsing the list of users, with the “up” and “down” arrows.
After choosing the right user name, the user must press the
key again. When it comes
to password, upon pressing the
key, the following characters will show up:
“
✳✳✳✳✳✳✳✳
”. The user must scroll for every letter in the password. After all the letters
are introduced (passwords are case sensitive) choose OK and press the
key again.
At successful Log on, the local HMI shows the new user name in the status bar at the
bottom of the LCD. If the Log on is OK, when required to change for example a password
protected setting, the local HMI returns to the actual setting folder. If the Log on has failed,
an "Error Access Denied" message opens. If a user enters an incorrect password three
times, that user will be blocked for ten minutes before a new attempt to log in can be
performed. The user will be blocked from logging in, both from the local HMI and
PCM600. However, other users are to log in during this period.
15.13
Authority status ATHSTAT
15.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Authority status
ATHSTAT
-
-
15.13.2
Application
Authority status (ATHSTAT) function is an indication function block, which informs
about two events related to the IED and the user authorization:
•
the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
•
the fact that at least one user is logged on (the output LOGGEDON)
The two outputs of ATHSTAT function can be used in the configuration for different
indication and alarming reasons, or can be sent to the station control for the same purpose.
Section 15
1MRK 511 286-UUS A
Basic IED functions
342
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...