One necessary component in the fault clearance system is the circuit breaker. It is from
practical and economical reason not feasible to duplicate the circuit breaker for the
protected component. Instead a breaker failure protection is used.
Breaker failure protection, 3-phase activation and output (CCRBRF, 50BF) will issue a
back-up trip command to adjacent circuit breakers in case of failure to trip of the “normal”
circuit breaker for the protected component. The detection of failure to break the current
through the breaker is made by means of current measurement or as detection of remaining
trip signal (unconditional).
CCRBRF (50BF) can also give a re-trip. This means that a second trip signal is sent to the
protected circuit breaker. The re-trip function can be used to increase the probability of
operation of the breaker, or it can be used to avoid back-up trip of many breakers in case
of mistakes during relay maintenance and test.
6.7.3
Setting guidelines
The parameters for Breaker failure protection 3-phase activation and output CCRBRF
(50BF) are set via the local HMI or PCM600.
The following settings can be done for the breaker failure protection.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Operation
:
Disabled
/
Enabled
FunctionMode
This parameter can be set
Current
or
Contact
. This states the way the
detection of failure of the breaker is performed. In the mode current the current
measurement is used for the detection. In the mode
Contact
the long duration of breaker
position signal is used as indicator of failure of the breaker. The mode
Current&Contact
means that both ways of detections are activated.
Contact
mode can be usable in
applications where the fault current through the circuit breaker is small. This can be the
case for some generator protection application (for example reverse power protection) or
in case of line ends with weak end infeed.
RetripMode
: This setting states how the re-trip function shall operate.
Retrip Off
means
that the re-trip function is not activated.
CB Pos Check
(circuit breaker position check) and
Current
means that a phase current must be larger than the operate level to allow re-trip.
CB Pos Check
(circuit breaker position check) and
Contact
means re-trip is done when
circuit breaker is closed (breaker position is used).
No CBPos Check
means re-trip is done
without check of breaker position.
1MRK 511 286-UUS A
Section 6
Current protection
131
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...