![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438148.webp)
Set value
Mode
Formula used for complex power calculation
A
*
A
A
S 3 V
I
= ×
×
EQUATION2044 V1 EN
(Equation 65)
B
*
B
B
S 3 V
I
= ×
×
EQUATION2045 V1 EN
(Equation 66)
C
*
C
C
S 3 V
I
= ×
×
EQUATION2046 V1 EN
(Equation 67)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
Enabled
/
Disabled
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
Section 6
1MRK 511 286-UUS A
Current protection
142
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...