12.8
Measured value expander block MVEXP
12.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
MVEXP
-
-
12.8.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and
VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI)
and IEC 61850 generic communication I/O functions (MVGGIO) are provided with
measurement supervision functionality. All measured values can be supervised with four
settable limits, that is low-low limit, low limit, high limit and high-high limit. The measure
value expander block (MVEXP) has been introduced to be able to translate the integer
output signal from the measuring functions to 5 binary signals, that is below low-low limit,
below low limit, normal, above high-high limit or above high limit. The output signals can
be used as conditions in the configurable logic.
12.8.3
Setting guidelines
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
12.9
Fault locator LMBRFLO
12.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator
LMBRFLO
-
-
Section 12
1MRK 511 286-UUS A
Monitoring
302
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...