The power system quantities provided, depends on the actual hardware,
(TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequence component quantities:
•
I: sequence currents (positive, zero, negative sequence, magnitude and angle)
•
V: sequence voltages (positive, zero and negative sequence, magnitude and angle).
The CVMMXN function calculates three-phase power quantities by using fundamental
frequency phasors (DFT values) of the measured current respectively voltage signals. The
measured power quantities are available either, as instantaneously calculated quantities
or, averaged values over a period of time (low pass filtered) depending on the selected
settings.
12.4.3
Setting guidelines
The available setting parameters of the measurement function CVMMXN, CMMXU,
VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,
CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Operation
:
Disabled
/
Enabled
. Every function instance (CVMMXN, CMMXU,
VMMXU, CMSQI, VMSQI, VNMMXU) can be taken in operation (
Enabled
) or out of
operation (
Disabled
).
The following general settings can be set for the
Measurement function
(CVMMXN).
PowMagFact
: Magnitude factor to scale power calculations.
PowAngComp
: Angle compensation for phase shift between measured I & V.
Mode
: Selection of measured current and voltage. There are 9 different ways of
calculating monitored three-phase values depending on the available VT inputs connected
to the IED. See parameter group setting table.
k
: Low pass filter coefficient for power measurement, V and I.
VMagCompY
: Magnitude compensation to calibrate voltage measurements at Y% of Vn,
where Y is equal to 5, 30 or 100.
1MRK 511 286-UUS A
Section 12
Monitoring
287
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...