t1
: Time delay of the re-trip. The setting can be given within the range 0 – 60s in steps of
0.001 s. Typical setting is 0 – 50ms.
t2
: Time delay of the back-up trip. The choice of this setting is made as short as possible
at the same time as unwanted operation must be avoided. Typical setting is 90 – 200ms
(also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
_
2
1
³ +
+
+
cbopen
BFP reset
margin
t
t
t
t
t
EQUATION1430 V1 EN
(Equation 58)
where:
t
cbopen
is the maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for breaker failure protection to detect correct breaker function (the
current criteria reset)
t
margin
is a safety margin
It is often required that the total fault clearance time shall be less than a given critical time.
This time is often dependent of the ability to maintain transient stability in case of a fault
close to a power plant.
1MRK 511 286-UUS A
Section 6
Current protection
133
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...