![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438321.webp)
Section 14
Station communication
14.1
IEC61850-8-1 communication protocol
14.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850-8-1 communication protocol
IEC 61850-8-1
-
-
14.1.2
Application
IEC 61850-8-1 communication protocol allows vertical communication to HSI clients
and allows horizontal communication between two or more intelligent electronic devices
(IEDs) from one or several vendors to exchange information and to use it in the
performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1
standard, allows the IEDs to communicate state and control information amongst
themselves, using a publish-subscribe mechanism. That is, upon detecting an event, the
IED(s) use a multi-cast transmission to notify those devices that have registered to receive
the data. An IED can, by publishing a GOOSE message, report its status. It can also
request a control action to be directed at any device in the network.
shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1
specifies only the interface to the substation LAN. The LAN itself is left to the system
integrator.
1MRK 511 286-UUS A
Section 14
Station communication
315
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...