WA1 (A)
WA2 (B)
189
189G
289G
989G
689
989
289
189G
289G
389G
689
389G
6289
6189
189G
289G
989G
989
BH_LINE_A
BH_LINE_B
BH_CONN
en04000513_ansi.vsd
152
152
152
ANSI04000513 V1 EN
Figure 118:
Switchyard layout breaker-and-a-half
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
10.4.8.2
Configuration setting
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE
and 1=TRUE:
•
989_OP = 1
•
989_CL = 0
Section 10
1MRK 511 286-UUS A
Control
252
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...