![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438185.webp)
1
PSM
2
Rs
(+)
(-)
HW
S W
PO1
TCS1
IS
V
IS: Constant current generator.
Current level ~ 1,0 mA (I
c
)
V: Transient Voltage Suppressor
Breakdown Voltage 380 to 400 VDC
I
c
CBPOS_open
TCSSCBR
TCS_STATE
BLOCK
ALARM
IEC13000026-2-en.vsd
GUID-6B09F9C7-86D0-4A7A-8E08-8E37CAE53249 V3 EN
Figure 67:
Operating principle of the trip-circuit supervision without an external
resistor. The circuit breaker open indication is set to block TCSSCBR
when the circuit breaker is open.
Trip-circuit monitoring and other trip contacts
It is typical that the trip circuit contains more than one trip contact in parallel, for example
in transformer feeders where the trip of a Buchholz relay is connected in parallel with the
feeder terminal and other relays involved.
1MRK 511 286-UUS A
Section 9
Secondary system supervision
179
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...