The
tMinSynch
is set to limit the minimum time at which synchronizing closing attempt
is given. The synchronizing function will not give a closing command within this time,
from when the synchronizing is started, even if a synchronizing condition is fulfilled.
Typical setting is
200
ms.
Synchrocheck settings
OperationSC
The
OperationSC
setting
Off
disables the synchronsim check function and sets the outputs
AUTOSYOK, MANSYOK, TSTAUTSY and TSTMANSY to low.
With the setting
Enabled
, the function is in service and the output signal depends on the
input conditions.
VDiffSC
Setting for voltage difference between line and bus in p.u. This setting in p.u is defined as
(measured V-Bus/VBase for bus according to
GblBaseSelBus
) - (measured V-Line/VBase
for line according to
GblBaseSelLine
). A typical value for the voltage difference can be
15%.
FreqDiffM
and
FreqDiffA
The frequency difference level settings,
FreqDiffM
and
FreqDiffA
, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the
FreqDiffM
setting is used. For auto-reclosing a
bigger frequency difference setting is preferable, where the
FreqDiffA
setting is used. A
typical value for the
FreqDiffM
can
10
mHz and a typical value for the
FreqDiffA
can be
100-200
mHz, when the synchronizing function is not used.
PhaseDiffM
and
PhaseDiffA
The phase angle difference level settings,
PhaseDiffM
and
PhaseDiffA
, shall also be
chosen depending on conditions in the network. The phase angle setting must be chosen
to allow closing under maximum load. A typical maximum value in heavy-loaded
networks can be 45 degrees whereas in most networks the maximum occurring angle is
below 25 degrees. The setting of
PhaseDiffA
setting is limited by the
PhaseDiffM
setting.
tSCM
and
tSCA
The purpose of the timer delay settings,
tSCM
and
tSCA
, is to ensure that the synchronism
check conditions remains constant and that the situation is not due to a temporary
interference. Should the conditions not persist for the specified time, the delay timer is
reset and the procedure is restarted when the conditions are fulfilled again. Circuit breaker
closing is thus not permitted until the synchronism check situation has remained constant
throughout the set delay setting time. Under stable conditions a longer operation time
delay setting is needed, where the
tSCM
setting is used. During auto-reclosing a shorter
Section 10
1MRK 511 286-UUS A
Control
196
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...