![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438277.webp)
11.1.3
Setting guidelines
The parameters for Tripping logic common 3-phase output SMPPTRC (94) are set via the
local HMI or through the Protection and Control Manager (PCM600).
The following trip parameters can be set to regulate tripping.
Operation
: Sets the mode of operation.
Disabled
switches the function off. The normal
selection is
Enabled
.
TripLockout
: Sets the scheme for lock-out.
Disabled
only activates the lock-out output.
Enabled
activates the lock-out output and latches the output
TRIP
. The normal selection
is
Disabled
.
AutoLock
: Sets the scheme for lock-out.
Disabled
only activates lock-out through the
input SETLKOUT.
Enabled
additonally allows activation through the trip function itself.
The normal selection is
Disabled
.
tTripMin
: Sets the required minimum duration of the trip pulse. It should be set to ensure
that the breaker is tripped correctly. Normal setting is
0.150s
.
11.2
Trip matrix logic TMAGGIO
11.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic
TMAGGIO
-
-
11.2.2
Application
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route trip
signals and other logical output signals to the tripping logics SMPPTRC and SPTPTRC
or to different output contacts on the IED.
TMAGGIO 3 output signals and the physical outputs allows the user to adapt the signals
to the physical tripping outputs according to the specific application needs for settable
pulse or steady output.
11.2.3
Setting guidelines
Operation
: Turns the operation of the function
Enabled
/
Disabled
.
1MRK 511 286-UUS A
Section 11
Logic
271
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...