in the protection IED monitors the healthy auxiliary relay coil, not the circuit breaker coil.
The separate trip circuit monitoring relay is applicable for this to supervise the trip coil of
the circuit breaker.
Dimensioning of the external resistor
Under normal operating conditions, the applied external voltage is divided between the
relay’s internal circuit and the external trip circuit so that at the minimum 20V (3...20 V)
remains over the relay’s internal circuit. Should the external circuit’s resistance be too
high or the internal circuit’s too low, for example due to welded relay contacts, the fault
is detected.
Mathematically, the operation condition can be expressed as:
(
)
20
C
ext
S
C
V
R
R
I
V DC
-
+
´
³
ANSIEQUATION16063 V1 EN
(Equation 92)
V
c
Operating voltage over the supervised trip circuit
I
c
Measuring current through the trip circuit, appr. 1.0 mA (0.85...1.20 mA)
R
ext
external shunt resistance
R
s
trip coil resistance
If the external shunt resistance is used, it has to be calculated not to interfere with the
functionality of the supervision or the trip coil. Too high a resistance causes too high a
voltage drop, jeopardizing the requirement of at least 20 V over the internal circuit, while
a resistance too low can enable false operations of the trip coil.
Table 13:
Values recommended for the external resistor R
ext
Operating voltage U
c
Shunt resistor R
ext
48 V DC
10 kΩ, 5 W
60 V DC
22 kΩ, 5 W
110 V DC
33 kΩ, 5 W
220 V DC
68 kΩ, 5 W
Due to the requirement that the voltage over the TCSSCBR contact must be 20V or higher,
the correct operation is not guaranteed with auxiliary operating voltages lower than 48V
DC because of the voltage drop in the R
ext
and operating coil or even voltage drop of the
feeding auxiliary voltage system which can cause too low voltage values over the
TCSSCBR contact. In this case, erroneous alarming can occur.
1MRK 511 286-UUS A
Section 9
Secondary system supervision
181
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...