INCosPhiPU
is the operate current level for the directional function when
OpModeSel
is
set
3I0Cosfi
. The setting is given in % of
IBase
. The setting should be based on calculation
of the active or capacitive ground-fault current at required sensitivity of the protection.
SN_PU
is the operate power level for the directional function when
OpModeSel
is set
3I03V0Cosfi
. The setting is given in % of
SBase
. The setting should be based on
calculation of the active or capacitive ground-fault residual power at required sensitivity
of the protection.
The input transformer for the Sensitive directional residual over current and power
protection function has the same short circuit capacity as the phase current transformers.
If the time delay for residual power is chosen the delay time is dependent on two setting
parameters.
SRef
is the reference residual power, given in % of
SBase
.
TDSN
is the time
multiplier. The time delay will follow the following expression:
inv
0
0
TDSN Sref
t
3I 3V cos (measured)
×
=
×
×
j
EQUATION2030-ANSI V1 EN
(Equation 57)
INDirPU
is the operate current level for the directional function when
OpModeSel
is set
3I0 and fi
. The setting is given in % of
IBase
. The setting should be based on calculation
of the ground-fault current at required sensitivity of the protection.
OpINNonDir
is set
Enabled
to activate the non-directional residual current protection.
INNonDirPU
is the operate current level for the non-directional function. The setting is
given in % of
IBase
. This function can be used for detection and clearance of cross-country
faults in a shorter time than for the directional function. The current setting should be
larger than the maximum single-phase residual current out on the protected line.
TimeChar
is the selection of time delay characteristic for the non-directional residual
current protection. Definite time delay and different types of inverse time characteristics
are available:
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
Table continues on next page
1MRK 511 286-UUS A
Section 6
Current protection
127
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...