Coordinated Universal Time (
UTC
)
•
Local time set in the master (
Local
)
•
Local time set in the master adjusted according to daylight saving time (
Local
with DST
)
•
TimeSyncMode
specifies the time sent by the IED. The time synchronisation is done
using the following ways:
•
IEDTime
: The IED sends the messages with its own time.
•
LinMasTime
: The IED measures the offset between its own time and the master
time, and applies the same offset for the messages sent as in the
IEDTimeSkew
.
But in
LinMasTime
it applies the time changes occurred between two
synchronised messages.
•
IEDTimeSkew
: The IED measures the offset in between its own time and the
master time and applies the same offset for the messages sent.
•
EvalTimeAccuracy
evaluates time accuracy for invalid time. Specifies the accuracy
of the synchronization (5, 10, 20 or 40 ms). If the accuracy is less than the specified
value, the “Bad Time” flag is raised. To accommodate those masters that are really
bad in time sync, the
EvalTimeAccuracy
can be set to
Disabled
.
According to the standard, the “Bad Time” flag is reported when synchronization has been
omitted in the protection for >23 h.
15.3
Parameter setting group handling
15.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Setting group handling
SETGRPS
-
-
Parameter setting groups
ACTVGRP
-
-
15.3.2
Application
Four different groups of settings are available to optimize IED operation for different
power system conditions. By creating and switching between fine tuned setting sets, either
from the local HMI or configurable binary inputs, results in a highly adaptable IED that
can cope with a variety of power system scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control IEDs to best provide for dependability, security and selectivity
requirements. Protection IEDs operate with a higher degree of availability, especially, if
1MRK 511 286-UUS A
Section 15
Basic IED functions
329
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...