operate very quickly for faults very close to the generation (and relay) point, for which
very high fault currents are characteristic.
The instantaneous phase overcurrent protection 3-phase output PHPIOC (50) can operate
in 10 ms for faults characterized by very high currents.
6.1.3
Setting guidelines
The parameters for instantaneous phase overcurrent protection 3-phase output PHPIOC
(50) are set via the local HMI or PCM600.
This protection function must operate only in a selective way. So check all system and
transient conditions that could cause its unwanted operation.
Only detailed network studies can determine the operating conditions under which the
highest possible fault current is expected on the line. In most cases, this current appears
during three-phase fault conditions. But also examine single-phase-to-ground and two-
phase-to-ground conditions.
Also study transients that could cause a high increase of the line current for short times. A
typical example is a transmission line with a power transformer at the remote end, which
can cause high inrush current when connected to the network and can thus also cause the
operation of the built-in, instantaneous, overcurrent protection.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Pickup
: Set operate current in % of
IBase
.
6.1.3.1
Meshed network without parallel line
The following fault calculations have to be done for three-phase, single-phase-to-ground
and two-phase-to-ground faults. With reference to figure
, apply a fault in B and then
calculate the current through-fault phase current I
fB
. The calculation should be done using
the minimum source impedance values for Z
A
and the maximum source impedance values
for Z
B
in order to get the maximum through fault current from A to B.
Section 6
1MRK 511 286-UUS A
Current protection
88
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...