![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438105.webp)
max
1.2
t
sc
high
I
k I
³
× ×
EQUATION1265 V1 EN
(Equation 32)
where:
1.2
is a safety factor
k
t
is a factor that takes care of the transient overreach due to the DC component of the fault current and
can be considered to be less than 1.1
Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.
The operate times of the phase overcurrent protection has to be chosen so that the fault
time is so short that protected equipment will not be destroyed due to thermal overload, at
the same time as selectivity is assured. For overcurrent protection, in a radial fed network,
the time setting can be chosen in a graphical way. This is mostly used in the case of inverse
time overcurrent protection. Figure
shows how the time-versus-current curves are
plotted in a diagram. The time setting is chosen to get the shortest fault time with
maintained selectivity. Selectivity is assured if the time difference between the curves is
larger than a critical time difference.
1MRK 511 286-UUS A
Section 6
Current protection
99
Application manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Страница 2: ......
Страница 26: ...20...
Страница 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Страница 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Страница 82: ...76...
Страница 92: ...86...
Страница 170: ...164...
Страница 176: ...170...
Страница 274: ...268...
Страница 288: ...282...
Страница 350: ...344...
Страница 369: ...363...