V
ref
I
dir
ANSI09000636-1-en.vsd
1
2
2
3
4
ANSI09000636 V1 EN
Figure 35:
Directional function characteristic
1. RCA = Relay characteristic angle 55°
2. ROA = Relay operating angle 80°
3. Reverse
4. Forward
6.2.3.1
Settings for steps 1 to 4
n
means step 1 and 4.
x
means step 1, 2, 3 and 4.
DirModeSelx
: The directional mode of step
x
. Possible settings are
Disabled
/
Non-
directional
/
Forward
/
Reverse
.
Section 6
1MRK 511 286-UUS A
Current protection
94
Application manual