Section 5
Local Human-Machine-Interface LHMI
5.1
Local HMI screen behaviour
5.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI screen behaviour
SCREEN
-
-
5.1.2
Settings
Table 12:
SCREEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
DisplayTimeout
10 - 120
Min
10
60
Local HMI display timeout
ContrastLevel
-100 - 100
%
10
0
Contrast level for display
DefaultScreen
0 - 0
-
1
0
Default screen
EvListSrtOrder
Latest on top
Oldest on top
-
-
Latest on top
Sort order of event list
AutoIndicationDRP
Disabled
Enabled
-
-
Disabled
Automatic indication of disturbance report
SubstIndSLD
No
Yes
-
-
No
Substitute indication on single line diagram
InterlockIndSLD
No
Yes
-
-
No
Interlock indication on single line diagram
BypassCommands
No
Yes
-
-
No
Enable bypass of commands
5.2
Local HMI signals
5.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI signals
LHMICTRL
-
-
1MRK 511 287-UUS A
Section 5
Local Human-Machine-Interface LHMI
61
Technical manual